Start-up and operation of the
position controller Type 8692
OUT ANALOG.-.Configuration.of.the.analogue.output
Only for the versions:
• one analogue output
• one analogue and two binary outputs
The feedback signal of the current position (
POS) or of the set-point value (CMD) can be transmitted to the control
centre via the analogue output.
SELEC
OUT POS
EXIT
OUT type
Output of the current position
OUT ANALOG
ENTER
OUT CMD
ENTER
Output of the set-point value
SELEC
4 - 20 mA
Selection of
the unit signal
EXIT
0 - 20 mA
0 - 10 V
0 - 5 V
Figure 69:
Operating structure OUTPUT-ANALOGUE
Changed values are not transferred into the memory (EEPROM) until the main menu (MAIN) is left.
OUT BIN1.-.Configuration.of.the.binary.output.1
OUT BIN2.-.Configuration.of.the.binary.output.2
The following description is valid for both binary outputs
OUT BIN 1 and OUT BIN 2, as the operation in the menu
is identical.
The binary outputs 1 and 2 can be used for one of the following outputs:
• Alarm output for excessively large control deviations of the position controller
• for the output of the current position with respect to a specified limit position (> or <)
• for the output: actuator in safety position
• for the output: sensor break
• for the output: operating state (AUTOMATIC / MANUAL)