Burkert Type 8693 User Manual

Page 178

background image

178

PROFIBUS-DP

30.5. process actual value (circular plug m8, 4-pole) -

only Type 8693

Switch
(behind the screw)

1

2

4

3

Process actual value

Circular.plug.M8,.4-pole

Figure 112: Connection - PROFIBUS-DP - Type 8693 - process actual value

Input.type

65)

Pin

Wire.
color

66)

Configuration

Switch

67)

External.circuit

4 – 20 mA
- internally
supplied

1
2
3
4

brown
white
blue
black

+ 24 V transmitter supply
Output from transmitter
GND
Bridge after GND (GND from
3-wire transmitter)

Switch on

left

GND

1
2

3
4

Transmitter

I

4 – 20 mA
- externally
supplied

1
2
3
4

brown
white
blue
black

not assigned
Process actual +
not assigned
Process actual -

Switch on

right

2

4

GND

4 – 20 mA

Frequency
- internally
supplied

1
2
3
4

brown
white
blue
black

+ 24 V sensor supply
Clock input +
Clock input - (GND)
not assigned

Switch on

left

1

2

3

+ 24 V

Clock +

Clock -

Frequency
- externally
supplied

1
2
3
4

brown
white
blue
black

not assigned
Clock input +
Clock input -
not assigned

Switch on

right

2

3

Clock -

Clock +

Pt 100
(see infor-
mation
below)

1
2
3
4

brown
white
blue
black

not assigned
Process actual 1 (current feed)
Process actual 2 (GND)
Process actual 3 (compensation) Switch on

right

Pt 100

2

3
4

Table 44:

Process actual value - Type 8693

For reasons of wire compensation connect the Pt 100 sensor via 3 wires. Always bridge PIN 3 and PIN 4
on the sensor.

65)

Can be adjusted by software (see chapter entitled “20.4. Procedure for specifying the basic settings”)

66)

The indicated colors refer to the connecting cable available as an accessory (92903474)

67)

The switch is situated behind the screw (see “Figure 110: ”)