beautypg.com

Burkert Type 8693 User Manual

Page 163

background image

163

Start-up and operation of the

position controller Type 8693

OUT ANALOG.-.Configuration.of.the.analogue.output

Only for the versions:

• one analogue output

• one analogue output and two binary outputs

The feedback of the current position (

POS), the position set-point value (CMD), the process actual value (PV) or

the process set-point value (

SP) can be transmitted to the control centre via the analogue output.

SELEC

Out POS

EXIT

OUT type

Output of the current position

OUT ANALOG

ENTER

Out CMD

Out PV

Out SP

ENTER

Output of the position set-point value

Output of the process actual value

Output of the process set-point value

SELEC

4 - 20 mA

Selection of
the unit signal

EXIT

0 - 20 mA

0 - 10 V

0 - 5 V

Figure 103: Operating structure OUTPUT-ANALOGUE-8693

Changed values are not transferred into the memory (EEPROM) until the main menu (MAIN) is left.

english

Type 8692, 8693

This manual is related to the following products: