PROFIBUS-DP
Address XXX
Input the device address
Press the arrow keys (+/-) to set values from 0 – 126;
Confirm by pressing the selection key on the right (OK).
BUS FAIL
SafePos off
SafePos on
Activate to approach the safety position if the bus communication fails
The position is approached which corresponds to the set-point value last trans-
ferred. (Default setting)
If
SafePos on is set, the following configurations may occur:
• Active
SAFEPOS
menu option If a fault is detected in the bus communication, the drive moves to
the lower
SAFEPOS set position.
• Inactive
SAFEPOS
menu option If a fault is detected in the bus communication, the drive moves to
the end position which it would specify in the isolated state.
BUS PDI
Position
CMD
Process value
70)
Setpoint
70)
Temperature
Operation mode
Errors
P.CONTRL active
71)
Selection of the process values which are to be transferred by the positioner to
the controller (master).
Press the selection key on the right (ENTER) either to activate (x) or deactivate
( ) the respective process value.
For meaning of the process values see table
PDI: Process Data Input.
BUS PDO
CMD / Setpoint
70)
Operation mode
Error reset
P.CONTRL active
71)
Selection of the process values which are to be transferred by the controller
(master) to the positioner.
Press the selection key on the right (ENTER) either to activate (x) or deactivate
( ) the respective process value.
For meaning of the process values see table
PDO: Process Data Output.
70)
only for type 8693 and when process controller activated
71)
only for type 8693
english
Type 8692, 8693