140

Start-up and operation of the
position controller Type 8693

K-Factor

TEACH IN

teach-in function:

Calculating the K-factor by measuring a specific flow rate.

Hold down the selection key on the right (ENTER) for approx. 3 s (countdown on display)

When this menu is entered, the valve is closed in order to have a defined initial state for implemen-
tation of the Teach-in function.

starting the measurement

Press the selection key on the right (START) to start the measurement (the message “

Teach-in at work”

is displayed briefly).

The valve is opened and the container is filled (“→

fill ..“ is indicated on the display).

ending the measurement

Press the selection key on the right (STOP) to complete the measurement and to display the input
screen for the volume.

inputting the position of the decimal point

The decimal point on the display has a dark background.

Press the up arrow key (+) to specify the position.

inputting the measured volume

Press the down arrow key (←) to highlight the individual positions with a dark background. Press the
up arrow key (+) to set the value.

Adjustment range: 0 ... 9999