. information.on.the.display, Information on the display – Burkert Type 8693 User Manual
Page 38
38
Control and display elements,
operating modes
12.3. information on the display
The following representation describes the information on the display:
Value
Bar graph display
of the value
MENU
INPUT
CMD
MANU
POS
%
XXX
Description of
the value
Unit or per-
centage of the
value
Display for AUTOMATIC mode:
Bar running from left to right
Configuration of the keys
Figure 12:
Description of display
List of values which can be displayed in AUTOMATIC mode:
Representation of
value
Unit, value range
Description
POS
%
Display of actual position of the valve actuator
CMD
%
Display of nominal position of the valve actuator
TEMP
°C
Internal temperature in the body of the positioner
INPUT
mA, V
Input signal for nominal position
PV (PROCESS
VALUE)
bar, mbar, psi, %, mm,
litre
l/s, l/min, l/h, m³/min,
m³/h, UG/s, UG/min,
UG/h, IG/s, IG/min, IG/h
°C, °F
Process actual value, 4 – 20 mA input
Process actual value, Frequency input
Process actual value, Pt 100 input
SP (SETPOINT)
bar, mbar, psi, %, mm,
litre
l/s, l/min, l/h, m³/min,
m³/h, UG/s, UG/min,
UG/h, IG/s, IG/min, IG/h
°C, °F
3)
Process set-point value
SP/PV(t)
Representation of process actual value and set-point value
Table 10:
Representation of value
3)
Unit depending on process actual value.
english