Installation
18.3.2. Output signals to the control centre (e.g. plc)
(required for analogue output and/or binary output option
only)
→
Connect the terminals according to the design (options) of the positioner.
Terminal Configuration
External.circuit
9
8
Analogue position feedback +
Analogue position feedback GND
9
8
GND
+ (0/4 – 20 mA or 0 – 5 / 10 V)
completely galvanically isolated
5
6
Binary output 1
Binary output GND
5
6
GND
24 V / 0 V NC / NO
7
6
Binary output 2
Binary output GND
7
6
GND
24 V / 0 V NC / NO
Table 21:
Configuration screw terminals - Output signals to the control centre
18.3.3. supply voltage
Terminal Configuration
External.circuit
14
13
Supply voltage +
Supply voltage GND
14
13
24 V DC ± 10 %max.
residual ripple 10 %
Table 22:
Configuration screw terminals - Supply voltage
When the supply voltage is applied, the positioner is operating.
→
Now implement the required basic settings and activate automatic adjustment of the positioner as described in
the chapter entitled “19. Initial start-up” or “Starting and setting up the position controller Type 8692”.