Description of system,
10.
inTerfaces Of The pOsiTiOner fOr The
mOdels WiTh caBle gland
Inputs for position or
process set-point value
4 – 20 mA
0 – 20 mA
0 – 10 V
0 – 5 V
Input for process actual
value
1)
4 – 20 mA
Frequency
Pt 100
Binary input
24 V DC
positioner
(Cable gland)
2 binary outputs
1)
(as an alternative to input
for process actual value)
Analogue position
feedback
Inputs
Outputs
Supply
Operation
Figure 9:
Interfaces for the model with cable gland
The positioners Type 8692 and Type 8693 are 3-wire devices, i.e. the power (24 V DC) is supplied separately
from the set-point value signal.
1)
Type 8693: The switch can be used to supply power to a connected sensor (description see “18.5.1 Terminal
assignment when selecting the process actual value input”)
english