. factory.settings.of.the.position.controller, Factory settings of the position controller – Burkert Type 8693 User Manual
Page 81

81
Start-up and operation of the
position controller Type 8692
20.3. factory settings of the position controller
Function... . .Factory.setting
Function... . .Factory.setting
ACTUATOR SINGLE or DOUBLE
16)
INPUT 4-20 mA
CHARACT linear
DIR.CMD Rise
CUTOFF Min 0 %
Max 100 %
DIR.ACT Rise
SPLTRNG Min 0 %
Max 100 %
X.LIMIT Min 0 %
Max 100 %
X.TIME
Open (1s) Values of X.TUNE determined
Close (1s) Values of X.TUNE determined
After running SET.FACTORY: 1s
BINARY. IN SafePos
BIN. IN type normally open
X.CONTROL
DBND
1.0 %
KXopn
(1) Values of
X.TUNE determined
KXcls
(1) Values of
X.TUNE determined
After running
SET.FACTORY: 1
SECURITY
Access Code 1 0000
SAFEPOS
0 %
SIG.ERROR
SP/CMD Input Error off
OUTPUT
17)
OUT
ANALOGUE
Out POS
OUT type 4-20 mA
OUT BIN1
Out DEV.X
Lim. DEV.X 1.0 %
OUT.BIN1 type normally open
OUT BIN2
Out DEV.X
Lim. DEV.X 1.0 %
OUT.BIN1 type normally open
Table 24:
Factory settings of the position controller
16)
Preset at the factory
17)
Option only
english
Type 8692, 8693