Start-up and operation of the
position controller Type 8693
If the
P.CONTROL auxiliary function is active for the process controller Type 8693, the following auxiliary func-
tions differ from those described for the position controller Type 8692 (highlighted in “Figure: 94”):
•
CUTOFF
•
SECURITY
•
SIG.ERROR
•
OUTPUT
•
CAL. USER
25.1.1. including auxiliary functions in the main menu
→
Press the arrow keys to select the
ADD.FUNCTION menu option in the main menu and press the right
selection key
(ENTER) to enter the submenu.
→
Press the arrow keys to select the required auxiliary function.
→
Press the selection key on the right (ENTER) to mark the auxiliary function with a cross (x).
→
All marked functions are transferred to the main menu when the selection key on the left (EXIT) is pressed.
→
In the main menu input the parameters of the auxiliary functions.
25.1.2. removing auxiliary functions from the main menu
If a function is removed from the main menu, the settings implemented previously under this function become
invalid again.
→
Press the arrow keys to select the
ADD.FUNCTION menu option in the main menu.
→
Enter the submenu by pressing the selection key on the right (ENTER).
→
Press the arrow keys to select an auxiliary function indicated with a cross (x).
→
Press the selection key on the right (ENTER) to remove the cross (x).
→
After pressing the selection key on the left (EXIT), the auxiliary function is deactivated and removed from the
main menu.
A precise description on the operation of the auxiliary functions can be found in the chapters entitled
"21.4. Specifying the basic settings" and in "22. Configuring the auxiliary functions".