. connection.diagram.type.8693, . supply.voltage.(circular.plug.m12,.4-pole), . bus.connection.(circular.plug.m12,.5-pole) – Burkert Type 8693 User Manual
Page 197: Connection diagram type 8693, Supply voltage (circular plug m12, 4-pole), Bus connection (circular plug m12, 5-pole)

197
DeviceNet
41.2. connection diagram Type 8693
Circular.plug.M12,.4-pole
Supply voltage
Switch (behind the screw)
1
2
3
4
1
2
4
3
Process actual value
Circular.plug.M8,.4-pole
Function earth (FE)
Circular.plug.M12,.5-pole
DeviceNet
1
2
3
4
5
Figure 121: Connection of DeviceNet - Type 8693
The supply voltage to the device is not supplied via the DeviceNet voltage V+ und V-, but via the supply
voltage galvanically isolated from the DeviceNet.
41.3. supply voltage (circular plug m12, 4-pole)
PIn
Configuration
External.circuit
1
+ 24 V
1
3
24 V DC ± 10 %
max. residual ripple 10 %
2
not used
3
GND
4
not used
Table 50:
Supply voltage
41.4. Bus connection (circular plug m12, 5-pole)
PIn
Signal
Color
1
Shielding
not used
2
V +
not used
3
V-
not used
4
CAN H
white
5
CAN L
blue
Table 51:
Bus connection
english