106

Start-up and operation of the
position controller Type 8692

22.3.7. X.LIMIT

limits the mechanical stroke range

This auxiliary function limits the (physical) stroke to specified % values (minimum and maximum). In doing so, the
stroke range of the limited stroke is set equal to 100 %. If the limited stroke range is left during operation, negative
POS values or POS values are indicated greater than 100 %.

Factory setting:

Min = 0%,

Max = 100%

X.LIMIT

Min 0 %

Max 100 %

EXIT

ENTER

INPUT

+

-

Min 0 %

OK

INPUT

+

-

Max 100 %

OK

26)

26)

Input the initial value of
the stroke range as %
Adjustment range:
0 – 50 % of the total
stroke

Input the final value of the
stroke range as %,
Adjustment range:
50 – 100 % of the total
stroke

The minimum gap between Min

and Max

is 50 %

Figure 58:

Operating structure X.LIMIT

Changed values are not transferred into the memory (EEPROM) until the main menu (MAIN) is left.

Limited
stroke

Unlimited
stroke

Physical
stroke (%)
(

POS)

Limited
stroke (%)
(

POS)

Set-point value
[mA] (

INPUT)

Adjustment range in MANUAL mode

Control range in

AUT

OMA

TIC mode

Figure 59:

Graph X.LIMIT

26)

if the sub-menu is left by pressing the selection key on the left (ESC), the value remains unchanged.