Start-up and operation of the

position controller Type 8693

23.6.4. SETUP - setting up the process controller

These functions specify the type of control.

PV INPUT - Indication of the signal type for the process actual value

The

PV INPUT function specifies the signal type of the process actual value:

• Unit signal

4 – 20 mA

Flow, pressure, level

• Frequency signal

0 – 1,000 Hz

Flow

• Circuit with Pt 100

-20 °C – +220 °C

temperature

Factory setting: 4 ... 20 mA

PV-INPUT

ENTER

SELEC

4-20 mA

Unit signal 4 – 20 mA (flow, pressure, level)

EXIT

Frequency

Frequency signal (flow) 0 – 1,000 Hz

PT 100

Circuit with Pt 100 (temperature)
-20 °C – +220 °C

Figure 84:

Operating structure P.CONTROL - PV-INPUT

PV-SCALE - Scaling of the process controller

The

PV-SCALE function specifies the following settings:

• The unit of the process actual value.

• The position of the decimal point.

• The values for the lower and upper process actual value.

If the settings for the unit of the process actual value or the position of the decimal point are input or
changed, this setting applies to all scaling values (

SPmin, SPmax, PVmin, PVmax).