Start-up and operation of the
position controller Type 8693
23.3. factory settings of the process controller
Function... . .. Factory.setting
Function... . .. . Factory.setting
P.CONTROL
PARAMETER
DBND
1.0 %
KP
1.00
TN
999.9
TV
0.0
X0
0.0 %
FILTER
0
SETUP
PV-INPUT
4-20 mA
PV SCALE
PVmin 0.0
PVmax 100.0
SP-INPUT
internal
P.CO-INIT
bumpless
Table 32:
Factory settings of the process controller
The factory settings of the position controller can be found in the chapter entitled "21.3. Factory settings
of the position controller".
23.4. procedure for setting up a process control
The.process.control.cannot.be.implemented.until.the.position.controller.has.been.automatically.
adjusted.(X.TUNE)!
Always observe the following sequence:
X.TUNE → P.Q‘LIN → P.TUNE.
To operate the positioner as a process controller, implement the following steps:
setting up the position controller:
→
Specify the standard settings of the positioner and automatically adjust the position controller
(
X.TUNE).
setting up the process controller:
→
Start the
P.CONTROL auxiliary function via the configuration menu in the main menu.
The
P.CONTROL function also inserts the P.Q’LIN function into the main menu.
→
Implement the standard settings for the process controller under
P.CONTROL.
Linearisation of the process characteristic
If this is a flow control process, the process characteristic can be linearised automatically:
→
Implement the
P.Q’LIN function.
Self-optimization of the process controller
→
Implement the
P.TUNE function.