beautypg.com

. factory.settings.of.the.process.controller, . procedure.for.setting.up.a.process.control, Factory settings of the process controller – Burkert Type 8693 User Manual

Page 129: Procedure for setting up a process control

background image

129

Start-up and operation of the

position controller Type 8693

23.3. factory settings of the process controller

Function... . .. Factory.setting

Function... . .. . Factory.setting

P.CONTROL
PARAMETER
DBND

1.0 %

KP

1.00

TN

999.9

TV

0.0

X0

0.0 %

FILTER

0

SETUP
PV-INPUT

4-20 mA

PV SCALE

PVmin 0.0

PVmax 100.0

SP-INPUT

internal

P.CO-INIT

bumpless

Table 32:

Factory settings of the process controller

The factory settings of the position controller can be found in the chapter entitled "21.3. Factory settings
of the position controller".

23.4. procedure for setting up a process control

The.process.control.cannot.be.implemented.until.the.position.controller.has.been.automatically.
adjusted.(X.TUNE)!

Always observe the following sequence:

X.TUNE P.Q‘LINP.TUNE.

To operate the positioner as a process controller, implement the following steps:

setting up the position controller:

Specify the standard settings of the positioner and automatically adjust the position controller
(

X.TUNE).

setting up the process controller:

Start the

P.CONTROL auxiliary function via the configuration menu in the main menu.

The

P.CONTROL function also inserts the P.Q’LIN function into the main menu.

Implement the standard settings for the process controller under

P.CONTROL.

Linearisation of the process characteristic

If this is a flow control process, the process characteristic can be linearised automatically:

Implement the

P.Q’LIN function.

Self-optimization of the process controller

Implement the

P.TUNE function.

english

Type 8692, 8693

This manual is related to the following products: