. other.malfunctions, Other malfunctions – Burkert Type 8693 User Manual
Page 221
221
Maintenance and troubleshooting
On.PrOFIBuS-DP:
Display
Device.status
Explanation
Troubleshooting
BUS offline
is displayed approx. every
3 seconds
offline
Device is not connected to the
bus
• Bus connection including
plug assignment correct.
• Check power supply and
bus connection of the other
nodes.
Table 66:
Error messages PROFIBUS-DP; Type 8693
50.2. Other malfunctions
Problem
Possible.causes
remedial.action
POS = 0 (when CMD > 0 %) or
POS = 100 %, (when CMD < 100 %)
PV = 0 (when SP > 0) or
PV = PV (when SP > SP )
Sealing function (
CUTOFF) has
been unintentionally activated
Deactivate sealing function
Applies only to devices with binary
output:
Binary output does not switch
Binary output:
Current > 100 mA
Short-circuit
Check binary output connection.
Applies only to devices with process
controller:
Device is not operating as a con-
troller, despite correctly implemented
settings.
P.CONTROL menu option is in
the main menu. The device is
therefore operating as a process
controller and expects a process
actual value at the corresponding
input.
Remove
P.CONTROL menu option
from the main menu.
Table 67:
Other malfunctions Type 8693