DeviceNet
44.2. static output assemblies
name
Address.of.data.attribute.of.the.assem-
blies.for.read.access..Class,.Instance,.
Attribute
Format.of.the.data.
attribute
INP (factory setting)
4, 21, 3
Byte 0: INP low
Byte 1: INP high
SP
4, 22, 3
Byte 0: SP low
Byte 1: SP high
Table 55:
Static output assemblies
The addresses indicated in the
Static Output Assemblies table can be used to specify a path for the Consumed
Connection Path attribute of an I/O connection, whereby the attributes described in more detail in the following
table can be transferred as output process data via this I/O connection. Nevertheless, by using this address data,
the attributes combined in the assemblies can also be accessed acyclically via
Explicit Messages .
name
Description.of.the.output.data.attributes
Attribute.Address.Class,.
Instance,.Attribute;..
Data.type,.Length
INP
Nominal position
Set-point value of position controller as ‰. Value range 0–1000.
In "pure" position controller mode (
P.CONTRL inactive) the
transfer of the nominal position
INP is required; as a process con-
troller (
PCONTRL active) the transfer of INP is not possible. If the
value is too small or too large, the last valid value is used and is
indicated in
ERR with HEX 14.
111, 1, 58;
UINT, 2 byte
SP
79)
Process set-point value
Set-point value of process controller in physical unit (as set in the
menu
P.CO INP or P.CO SCAL), max. value range –999–9999,
depending on internal scaling.
If the value is too small or too large, the last valid value is used and
is indicated in
ERR with HEX 15.
120, 1, 2;
INT, 2 byte
Table 56:
79)
relevant only for type 8693 and when process controller activated.
english
Type 8692, 8693