Start-up and operation of the
position controller Type 8693
23.2. description of the procedure
When the operating voltage has been switched on, the positioner is at the process operating level in the AUTOMATIC
operating state.
To specify the basic settings, you must switch to the configuration level:
→
Hold down the left selection key (MENU) for approx. 3 seconds (wait for countdown on display).
Then the main menu is indicated on the display (MAIN).
→
Press the arrow keys to switch between the main menu options and select a menu option with the right selection key
(ENTER/RUN).
Depending on the function, a menu sub-option or a selection screen is indicated on the display.
→
Press the arrow keys to switch between these sub-options and select the required settings. Press the right
selection key (SELEC/ENTER) to confirm the selection (the point after the selected parameter is now marked).
Return to the main menu by pressing the left selection key (EXIT).
→
To save the changed settings, you must leave the configuration level by pressing the left selection key (EXIT).
You are back at the process operating level.
Only when you leave the configuration level by pressing the right selection key, are the changed parameters
and settings saved (
“save EEPROM”).
•
english