background image

170

Start-up and operation of the
position controller Type 8693

calibr. PV Calibrating.the.process.actual.value.(4.–.20.mA.or.Pt.100):....

4 – 20 ma:

calibr. PV

ENTER

PV 4mA 0

EXIT

PV 4mA 0

61)

INPUT

OK

62)

PV 20mA 0

PV 20mA 0

61)

INPUT

OK

62)

Figure 106: Operating structure CAL.USER-8693-PV-4-20

In the

CAL. USER menu press the arrow keys to select the calibr. PV menu option and confirm with the selection

key on the right (ENTER).

Accept the minimum input signal (4 mA):

Press the arrow keys to select the

PV 4 mA menu option and confirm with the selection key on the right (INPUT).

Apply the minimum value of the unit signal on the input and confirm by pressing the selection key on the right (OK).

Accept the maximum input signal (20 mA):

Press the arrow keys to select the

PV 20 mA menu option and confirm with the selection key on the right (INPUT).

Apply the maximum value of the unit signal on the input and confirm by pressing the selection key on the right (OK).

61)

The signal type is displayed which is selected in the INPUT menu (4 – 20 mA; 0 – 20 mA; 0 – 5 V; 0 – 10 V).

62)

If the sub-menu is left by pressing the selection key on the left (ESC), the value remains unchanged