Start-up and operation of the
position controller Type 8693
calibr. PV Calibrating.the.process.actual.value.(4.–.20.mA.or.Pt.100):....
4 – 20 ma:
calibr. PV
ENTER
PV 4mA 0
EXIT
PV 4mA 0
61)
INPUT
OK
62)
PV 20mA 0
PV 20mA 0
61)
INPUT
OK
62)
Figure 106: Operating structure CAL.USER-8693-PV-4-20
→
In the
CAL. USER menu press the arrow keys to select the calibr. PV menu option and confirm with the selection
key on the right (ENTER).
Accept the minimum input signal (4 mA):
→
Press the arrow keys to select the
PV 4 mA menu option and confirm with the selection key on the right (INPUT).
→
Apply the minimum value of the unit signal on the input and confirm by pressing the selection key on the right (OK).
Accept the maximum input signal (20 mA):
→
Press the arrow keys to select the
PV 20 mA menu option and confirm with the selection key on the right (INPUT).
→
Apply the maximum value of the unit signal on the input and confirm by pressing the selection key on the right (OK).
61)
The signal type is displayed which is selected in the INPUT menu (4 – 20 mA; 0 – 20 mA; 0 – 5 V; 0 – 10 V).
62)
If the sub-menu is left by pressing the selection key on the left (ESC), the value remains unchanged