Start-up and operation of the
position controller Type 8693
23.5. setting up the position controller
Specification of the basic settings is described in the chapter entitled "21.4. Specifying the basic settings".
When starting up the positioner for the first time, implement the following basic settings:
→
Specify the selected unit signal input for the set-point value default (
INPUT)
(4 – 20 mA, 0 – 20 mA, 0 – 10 V or 0 – 5 V).
→
Start automatic adjustment of the position controller to the particular operating conditions (
X.TUNE).
The exact description of the functions
INPUT and X.TUNE can be found in the chapter entitled "21.5.
Description of the functions of the main menu”
.
The basic settings for the positioner are implemented at the factory.
During start-up, however, it is essential to input the unit signal (
INPUT) and run X.TUNE . Using the
X.TUNE function, the positioner automatically determines the optimum settings for the current operating
conditions.
23.6. setting up the process controller
23.6.1. starting the P.CONTROL auxiliary function
How to start the auxiliary functions is described in the chapter entitled "22. Configuring the auxiliary
functions".
→
Press the left selection key (MENU) to switch to the configuration level in the main menu (MAIN).
→
Press the arrow keys to select the
ADD.FUNCTION menu option and confirm by pressing the right selection
key (ENTER).
→
Press the arrow keys to select the
ADD.FUNCTION menu option and confirm by pressing the right selection
key (ENTER).
→
Press the left selection key (EXIT) to return to the main menu.
The main menu now contains the
P.CONTROL, P.Q‘LIN and P.TUNE auxiliary functions.