Tn - reset time of the process controller, Tv - hold-back time of the process controller – Burkert Type 8693 User Manual
Page 133

133
Start-up and operation of the
position controller Type 8693
KP - Amplification factor of the process controller
The amplification factor specifies the P-contribution of the PID controller.
Factory setting: 1.00
+
←
KP 1.00
KP 1.00
INPUT
OK
38)
Adjustment range:
0 – 99.99
(% / set unit)
Figure 79:
Operating structure P.CONTROL - KP
The
KP amplification of the process controller refers to the scaled unit.
TN - Reset time of the process controller
Specifies the I-contribution of the PID controller.
Factory setting: 999.9 s
+
←
TN 999.9
TN 0.5
INPUT
OK
38)
Adjustment range:
0.5 – 999.9 s
Figure 80:
Operating structure P.CONTROL - TN
TV - Hold-back time of the process controller
Specifies the D-contribution of the PID controller.
Factory setting: 0.0 s
+
←
TV 0.0
TV 0.0
INPUT
OK
38)
Adjustment range:
0 – 999.9 s
Figure 81:
Operating structure P.CONTROL - TV
38)
If the sub-menu is left by pressing the selection key on the left (ESC), the value remains unchanged.
english
Type 8692, 8693