33
Description of system,
Input resistance
180 Ω at 4 – 20 mA / 12 bit resolution
for actual value signal
17 kΩ at frequency, 0 – 1000 Hz / 1‰ of measured value
> 300 mV
ss
sine, square, triangle
Pt 100 -20 – +220 °C, resolution < 0.1 °C
Input resistance
180 Ω at 0/4 – 20 mA / 12 bit resolution
for nominal value signal
19 kΩ at 0 – 5/10 V / 12 bit resolution
Protection class
3 in accordance with VDE 0580
Analogue position feedback
max. current
for voltage output 0 – 5/10 V 10 mA
max. load
for current output 0/4 – 20 mA 560 Ω
Inductive proximity switches
current limitation
100 mA
Binary outputs
galvanically isolated
Current limiting
100 mA, output is clocked
Binary input
galvanically isolated
0 – 5 V = log "0", 10 – 30 V = log "1"
input inverted accordingly
11.3.6. pneumatic data
Control medium
neutral gases, air
Quality classes in accordance with DIN ISO 8573-1
Dust content
Class 5
max. particle size 40 µm, max. particle density 10 mg/m³
Water content
Class 3
max. pressure dew point
-20 °C or min. 10 degrees below the lowest operating temperature
Oil content
Class 5
max. 25 mg/m³
Temperature range
0 – +50 °C
Pressure range
3 – 7 bar
Air output, pilot valve
7 l
N
/ min (for aeration and deaeration)
(Q
Nn
value according to definition for pressure drop from 7 to 6 bar absolute)
Optional:
130 l
N
/ min (for aeration and deaeration)
(only single-acting)
Connections
Plug-in hose connector Ø 6mm / 1/4”
Socket connection G1/8
english