Burkert Type 8693 User Manual
Page 169
169
Start-up and operation of the
position controller Type 8693
procedure:
calibr. POS Calibrating.the.actual.value.display.POS (0.-.100.%):.....
→
In the
CAL. USER menu press the arrow keys to select the calibr. POS menu option and confirm with the
selection key on the right (ENTER).
Accept the minimum position:
→
Press the arrow keys to select the
POS lower X menu option and confirm with the selection key on the right
(INPUT).
→
Approach the minimum position of the valve using the arrow keys (OPN/CLS) and confirm this value by pressing
the selection key on the right (OK).
Accept the maximum position:
→
Press the arrow keys to select the
POS upper X menu option and confirm with the selection key on the right
(INPUT).
→
Approach the maximum position of the valve using the arrow keys (OPN/CLS) and confirm this value by pressing
the selection key on the right (OK).
calibr. SP
59).
Calibrating.the.process.set-point.value.(4.–.20.mA;.0.–.20.mA;.0.–.5.V;.0.–.10.V):.....
→
In the
CAL. USER menu press the arrow keys to select the calibr. SP menu option and confirm with the selection
key on the right (ENTER).
Accept the minimum input signal (0 mA; 4 mA; 0 V)
60)
:
→
Press the arrow keys to select the S
P (0 mA; 4 mA; 0 V)
60)
menu option and confirm with the selection key on the right
(INPUT).
→
Apply the minimum value of the unit signal on the input and confirm by pressing the selection key on the right (OK).
Accept the maximum input signal (20 mA; 5 V; 10 V)
60)
:
→
Press the arrow keys to select the SP (20 mA; 5 V; 10 V) menu option and confirm with the selection key on the right
(INPUT).
→
Apply the maximum value of the unit signal on the input and confirm by pressing the selection key on the right (OK).
59)
Only if external set-point value default is set in the P.CONTROL / SETUP / SP-INPUT
60)
The signal type is displayed which is selected in the INPUT menu (4 – 20 mA; 0 – 20 mA; 0 – 5 V; 0 – 10 V).
english
Type 8692, 8693