Technical.data, Technical data – Burkert Type 8693 User Manual
Page 194
194
DeviceNet
38.
Technical daTa
eds file
BUER8692.EDS
icons
BUER8692.ICO
Baudrate
125 kbit/s, 250 kbit/s, 500 kbit/s (can be adjusted by pressing operator keys on the device
or via network);
Factory setting 125 kbit/s
address
0 – 63; (can be adjusted by pressing operator keys on the device or via network);
Factory setting 63
process data
7 static input assemblies
(Input: from the positioner to the DeviceNet master/scanner)
4 static output assemblies
total line length
according to DeviceNet Specification
(Total line length = total of all trunk and drop lines)
Baudrate
maximum total line length
thick cable
thin cable
125 kbaud
500 m
100 m for all baudrates
250 kbaud
250 m
500 kbaud
100 m
Table 48:
Total line length
drop line length
Baudrate
length of the drop lines
maximum length
maximum total length
drop lines in the network
125 kbaud
6 m for all baudrates
156 m
250 kbaud
78 m
500 kbaud
39 m
Table 49:
Drop line length
english
Type 8692, 8693