Control and display elements,
operating modes
13.1. auTOmaTic operating state for Type 8692
(Bar runs along the upper edge of the display from left to right)
Normal controller mode is implemented and monitored in AUTOMATIC operating state.
The arrow keys can be used to switch between the following displays in AUTOMATIC operating state:
MENUINPUT CMD MANU
POS
%
XXX
Display of actual position of the valve actuator
(0 - 100%)
MENU POS TEMP MANU
CMD
%
XXX
• Display of nominal position of the valve actuator or
• Display of nominal position of the valve actuator after
rescaling by possibly activated split range function or
correction characteristic
(0 - 100%)
MENU CMD INPUT
TEMP
*C
XX.X
Internal temperature in the housing of the positioner
( °C)
MENU TEMP POS
INPUT
mA
XXX
Input signal for nominal position
(0 - 5/10 V or 0/4 – 20 mA)
Table 11:
AUTOMATIC operating state for Type 8692
13.2. auTOmaTic operating state for Type 8693
(Bar runs along the upper edge of the display from left to right)
Normal controller mode is implemented and monitored in AUTOMATIC operating state.
If the
P.CONTROL additional function is activated for Type 8693, it is possible to switch between the following
states in AUTOMATIC operating state: