beautypg.com

Burkert Type 8693 User Manual

Page 166

background image

166

Start-up and operation of the
position controller Type 8693

OUT DEV.X alarm output for excessively large control deviation of the position controller:

Press the arrow keys to mark the

OUT DEV.X menu option and confirm with the selection key on the right

(SELEC).

Press the arrow keys to input

the limit value for the permitted control deviation in the Lim. DEV.X 1.0% menu

option and accept with the selection key on the right (OK).

The permitted control deviation

Lim. DEV.X XX must not be less than the dead band.

In the

OUT BIN type menu option input the required switching status (normally open / normally closed, see

“Table 41: “).

OUT POS output of the current position with respect to a specified limit position:

Press the arrow keys to mark the

OUT POS menu option and confirm with the selection key on the right

(SELEC).

Press the arrow keys to input the

the value of the limit position in the Lim. POS 0% menu option and accept

with the selection key on the right (OK).

In the

OUT BIN type menu option input the required switching status (normally open / normally closed, see

“Table 41: “).

OUT BIN1

normally open

normally closed

POS > LIM

0 V

24 V

POS < LIM

24 V

0 V

Table 40:

OUT Safepos output of message: actuator in safety position:

Press the arrow keys to mark the

OUT Safepos menu option and confirm with the selection key on the right

(SELEC).

In the

OUT BIN type menu option input the required switching status (normally open / normally closed).

OUT ERR SP/CMD

55)

output sensor break:

Press the arrow keys to mark the

OUT ERR SP/CMD menu option and confirm with the selection key on the

right
(SELEC).

In the

OUT BIN type menu option input the required switching status (normally open / normally closed).

OUT ERR PV

55)

output sensor break:

Press the arrow keys to mark the

OUT ERR PV menu option and confirm with the selection key on the right

(SELEC).

In the

OUT BIN type menu option input the required switching status (normally open / normally closed).

55)

Only possible if signal level fault detection activated (see chapter entitled “25.4. SIG-ERROR Configuration of
signal level fault detection”)

english

Type 8692, 8693

This manual is related to the following products: