Start-up and operation of the
position controller Type 8693
OUT DEV.X alarm output for excessively large control deviation of the position controller:
→
Press the arrow keys to mark the
OUT DEV.X menu option and confirm with the selection key on the right
(SELEC).
→
Press the arrow keys to input
the limit value for the permitted control deviation in the Lim. DEV.X 1.0% menu
option and accept with the selection key on the right (OK).
The permitted control deviation
Lim. DEV.X XX must not be less than the dead band.
→
In the
OUT BIN type menu option input the required switching status (normally open / normally closed, see
“Table 41: “).
OUT POS output of the current position with respect to a specified limit position:
→
Press the arrow keys to mark the
OUT POS menu option and confirm with the selection key on the right
(SELEC).
→
Press the arrow keys to input the
the value of the limit position in the Lim. POS 0% menu option and accept
with the selection key on the right (OK).
→
In the
OUT BIN type menu option input the required switching status (normally open / normally closed, see
“Table 41: “).
OUT BIN1
normally open
normally closed
POS > LIM
0 V
24 V
POS < LIM
24 V
0 V
Table 40:
OUT Safepos output of message: actuator in safety position:
→
Press the arrow keys to mark the
OUT Safepos menu option and confirm with the selection key on the right
(SELEC).
→
In the
OUT BIN type menu option input the required switching status (normally open / normally closed).
OUT ERR SP/CMD
55)
output sensor break:
→
Press the arrow keys to mark the
OUT ERR SP/CMD menu option and confirm with the selection key on the
right
(SELEC).
→
In the
OUT BIN type menu option input the required switching status (normally open / normally closed).
OUT ERR PV
55)
output sensor break:
→
Press the arrow keys to mark the
OUT ERR PV menu option and confirm with the selection key on the right
(SELEC).
→
In the
OUT BIN type menu option input the required switching status (normally open / normally closed).
55)
Only possible if signal level fault detection activated (see chapter entitled “25.4. SIG-ERROR Configuration of
signal level fault detection”)