Inputting the input signal – Burkert Type 8693 User Manual
Page 84

84
Start-up and operation of the
position controller Type 8692
20.5.2. inputting the operating mode of the pneumatic actuator
ACTUATOR - Operating mode of the actuator
The operating mode of the pneumatic valve actuator used in combination with the positioner can be input in this
menu option.
The operating mode of the actuator has been preset at the factory.
CFA and CFB:
single-acting
CFI:
double-acting
The control function of the actuator can be found on the type label.
ACTUATOR
ENTER
SELEC
SINGLE
EXIT
DOUBLE
• single-acting
• double-acting
Figure 37:
Operating structure of ACTUATOR
20.5.3. inputting the input signal
INPUT - Selected unit input signal
→
Under this menu option input the unit signal used for the set-point value.
INPUT
SELEC
4-20 mA
EXIT
ENTER
0-20 mA
0-10 V
0- 5 V
• Current 4 – 20 mA
• Current 0 – 20 mA
• Voltage 0 – 10 V
• Voltage 0 – 5 V
Figure 38:
Operating structure of INPUT
english
Type 8692, 8693