Burkert Type 8693 User Manual
Page 118

118
Start-up and operation of the
position controller Type 8692
OUT DEV.X alarm output for excessively large control deviation of the position controller:
→
Press the arrow keys to mark the
OUT DEV.X menu option and confirm with the selection key on the right
(SELEC).
→
Press the arrow keys to input
the limit value for the permitted control deviation in the Lim. DEV.X menu option
and accept with the selection key on the right (OK).
The permitted control deviation
Lim. DEV.X XX must not be less than the dead band.
→
In the
OUT BIN type menu option input the required switching status (normally open / normally closed)
33)
.
OUT POS output of the current position with respect to a specified limit position:
→
Press the arrow keys to mark the
OUT POS menu option and confirm with the selection key on the right
(SELEC).
→
Press the arrow keys to input the
the value of the limit position in the Lim. POS 0% menu option and accept
with the selection key on the right (OK).
→
In the
OUT BIN type menu option input the required switching status (normally open / normally closed)
33)
.
OUT BIN1
normally open
normally closed
POS > LIM
0 V
24 V
POS < LIM
24 V
0 V
Table 30:
Switching status
OUT Safepos output of message: actuator in safety position:
→
Press the arrow keys to mark the
OUT Safepos menu option and confirm with the selection key on the right
(SELEC).
→
In the
OUT BIN type menu option input the required switching status (normally open / normally closed)
33)
.
OUT ERR SP/CMD output sensor break:
→
Using the arrow keys, mark the
OUT ERR SP/CMD menu option and confirm with the selection key on the
right (SELEC).
→
In the
OUT BIN type menu option input the required switching status (normally open / normally closed)
33)
.
english
Type 8692, 8693