beautypg.com

Cutoff – Burkert Type 8693 User Manual

Page 156

background image

156

Start-up and operation of the
position controller Type 8693

25.2. CUTOFF -

sealing function for the position controller Type
8693

This function causes the valve to be sealed outside the control area.

This is where you input the limits for the position set-point value (

CMD) as a percentage or for the process set-

point value (

SP) as a percentage of the scaling range, from which the actuator is fully deaerated or aerated. Control

mode opens or resumes at a hysteresis of 1 %. If the process valve is in the sealing area, the message

"CUTOFF

ACTIVE" is indicated on the display.

Factory setting:

Min= 0 %; Max = 100 %;

CUT type = Type PCO

CUTOFF

Min 0 %

Max 100 %

EXIT

ENTER

INPUT

+

-

Min 0 %

OK

INPUT

+

-

Max 100 %

OK

51)

51)

Sealing threshold
Deaeration (0 = not
active)
Adjustment range:
0 – 25 %
Sealing threshold
Aeration (100 = not
active)
Adjustment range:
75 – 100 %

CUT type

ENTER

SELEC

Type PCO

Select process
set-point value

EXIT

Type XCO

Select position
set-point value

Figure 97:

Operating structure CUTOFF-8693

Changed values are not transferred into the memory (EEPROM) until the main menu (MAIN) is left.

51)

If the sub-menu is left by pressing the selection key on the left (ESC), the value remains unchanged.

english

Type 8692, 8693

This manual is related to the following products: