AutoMax Programming Executive Version 3.x
operating system(s) to be loaded at 19200 baud. If the leftmost
Processor in the rack is a M/N 57C430A or M/N 57C431, the
operating system(s) will be loaded at 9600 baud. At 9600 baud, it will
require approximately two minutes to load each operating system to
the Processors in the rack. If there are 6010/6011 and 7010
Processors in the same rack, it will take approximately twice as long
as it would if there were only one type of Processor in the rack. The
UDC operating system requires approximately four minutes to load to
each UDC module in the rack.
What to Do Next
After loading the appropriate operating systems to the rack following
the instructions below, you would normally load compiled application
tasks and (optionally) UDC drive parameters to the rack. See section
14.3 for more information.
5.4.3.1
Procedure for Loading All Operating Systems to the Rack
The flowchart in figure 5.15 illustrates the options you have when
loading the AutoMax operating systems and UDC operating systems
(if DPS drive software has been installed). Before loading the
operating system(s), review this flowchart carefully.
Use the steps that follow to initiate the Load Operating Systems
procedure.
Step 1.
If you have not already done so, turn on the personal
computer and run the AutoMax Programming Executive
by typing
AUTOMAX3
Step 2.
Turn on power to the rack. Note that if the AutoMax
Processors in the rack do not have an operating system,
the leftmost AutoMax Processor module in the rack will
display the letters L" and O" (reading top to bottom).
This code prompts you to load the operating system.
Because Processor modules have onboard battery
backup, you will need to load the operating system only
when enhancements become available, when you change
the password for the rack using the PWOS.EXE utility
described in 9.2.1, or when a Processor module in the
rack is replaced.
Step 3.
Connect the personal computer to the leftmost AutoMax
Processor in the rack, following the directions in
section 3.4.
Step 4.
Select the system for which you want to load operating
system(s).
Step 5.
Select Load OS Single Rack from the Commands menu.
You will see the following message.
Connect cable to processor. Depress ENTER key when
ready, ESC key to abort.
Step 6.
Press ENTER.
The Programming Executive will establish communication with the
local rack and will determine the type(s) of AutoMax Processors in
the rack. It will also determine whether operating systems are
currently loaded to the Processors in the rack.