beautypg.com

Rockwell Automation 57C650 AutoMax Programming Executive Version 3.8 User Manual

Page 65

background image

5Ć9

Using the System Configurator

example, A00) indicates which network is primary (in this example,

A). The description, engineer, and customer data for the system and

each rack are transferred from the ASD file. Import adds racks using

the same process as for importing an AutoMax Version 2 rack.
The Import procedure will add as many modules to the rack as

possible based on the definition type found for a given slot (see

section 5.1.8.1 for information regarding module types). Import will

add the variables and their descriptions defined in the configuration

task. The networkĆwide variable names will be added using the .NET

files, if any. .NET files define network addresses for GBLDEF

variables in configuration tasks.
The tasks (name, type, priority, critical flag, and Processor slot)

defined in the configuration task will also be added. Task source files

will be copied into the AutoMax Executive system. Note that tasks

must successfully compile in ASD in order to import properly. Since

BASIC include files (.INC) are treated as tasks in the AutoMax

Executive software, a task is added for each include file found. Import

will also copy and rename any system, rack, or task documentation

files from the ASD system into the AutoMax Executive system. The

CPU documentation files in the ASD system will be copied into

AutoMax Executive system, but they can be accessed by the

AutoMax Executive software only by using Edit File from the

Commands menu. You may want to copy pertinent information into

the documentation files for the appropriate racks.

5.1.8.1

Module Types Recognized by the Import Procedure
Import will add as many modules as possible from the variable

definition statements in the configuration task. The following list

shows the modules added for the type of definition found.

Definition Found

Type of Module Added

NETDEF or GBLDEF 57C404 Network Communications
MODDEF

57C414 Modbus interface

RIODEF

57C416 Remote I/O Communications

(in the master rack)

RNETDEF

57C417 AutoMate interface

ABDEF

57C418 AB interface

TASK

57C430 AutoMax Processor

IODEF

Generic module (unless one of

the other definitions is found

for the slot)

5.1.8.2

Generic Modules
A generic" module, identified by the prefix GEN", is added to the

appropriate slot in the local rack when IODEF statements are the only

statements found for the slot in the configuration task. The generic

module is used because the IODEF statement does not provide

enough information to determine the specific type of module used.

Note also that for a remote I/O network, no hardware is added to the

rack database for the same reason.