13Ć2

AutoMax Programming Executive Version 3.x

The Software ID" depends on the version of the software (operating

system) that has been loaded to the AutoMax Processor. (Refer to

section 1.4.2 for a list of the software part numbers for versions of the

AutoMax Programming Executive.) If the Ethernet version of the

operating system is loaded, ENET" will be displayed on the line as

well. STD" will be displayed for the standard operating system.

Clock Tick" refers to the speed of the realĆtime clock. CPU

Utilization" shows the percentage of the AutoMax Processor currently

being used to run application tasks. Note that the CPU Utilization

percentage is measured over a two second time window. This value

should be kept under 80% to ensure that there are no overlaps in

AutoMax task execution.
Memory statistics for the AutoMax Processor and Common Memory

module are given in bytes. The field Largest Free block" refers to the

largest continuous block of memory available. The Battery" field

refers to the status of the onĆboard battery.

UDC Module

Figure 13.2 shows a sample display for a UDC module in slot 6.

ON LINE direct

AUTOMAX

C: \RPE\V33

EscăExit

Info/Log

UDC Information for Slot 4

Software ID: 422544Ć044A Tick Rate (micro sec): 500

Parameter File Date/Time: 03Ć08Ć1993 10:59:48a

UDC Utilization: 20%

Memory

Memory

Used

Free

Task A

2642

17838

Bytes

Task B

0

20480

Bytes

COMMON

128

12160

Bytes

PMIĆA OS Status: SD3000

PMIĆB OS Status: SV3000

PMIĆA Parameters: Installed

PMIĆB Parameters: Installed

PMIĆA Slot 0: PMI Processor

PMIĆB Slot 0: PMI Processor

PMIĆA Slot 1: Resolver & Drive I/O

PMIĆB Slot 1: Resolver & Drive I/O

PMIĆA Slot 2: DC Power Technology

PMIĆB Slot SV3000

Figure 13.2 Ć Info/Log UDC Information Display