Rockwell Automation 57C650 AutoMax Programming Executive Version 3.8 User Manual
Page 172
13Ć2
AutoMax Programming Executive Version 3.x
The Software ID" depends on the version of the software (operating
system) that has been loaded to the AutoMax Processor. (Refer to
section 1.4.2 for a list of the software part numbers for versions of the
AutoMax Programming Executive.) If the Ethernet version of the
operating system is loaded, ENET" will be displayed on the line as
well. STD" will be displayed for the standard operating system.
Clock Tick" refers to the speed of the realĆtime clock. CPU
Utilization" shows the percentage of the AutoMax Processor currently
being used to run application tasks. Note that the CPU Utilization
percentage is measured over a two second time window. This value
should be kept under 80% to ensure that there are no overlaps in
AutoMax task execution.
Memory statistics for the AutoMax Processor and Common Memory
module are given in bytes. The field Largest Free block" refers to the
largest continuous block of memory available. The Battery" field
refers to the status of the onĆboard battery.
UDC Module
Figure 13.2 shows a sample display for a UDC module in slot 6.
ON LINE direct
AUTOMAX
C: \RPE\V33
EscăExit
Info/Log
UDC Information for Slot 4
Software ID: 422544Ć044A Tick Rate (micro sec): 500
Parameter File Date/Time: 03Ć08Ć1993 10:59:48a
UDC Utilization: 20%
Memory
Memory
Used
Free
Task A
2642
17838
Bytes
Task B
0
20480
Bytes
COMMON
128
12160
Bytes
PMIĆA OS Status: SD3000
PMIĆB OS Status: SV3000
PMIĆA Parameters: Installed
PMIĆB Parameters: Installed
PMIĆA Slot 0: PMI Processor
PMIĆB Slot 0: PMI Processor
PMIĆA Slot 1: Resolver & Drive I/O
PMIĆB Slot 1: Resolver & Drive I/O
PMIĆA Slot 2: DC Power Technology
PMIĆB Slot SV3000
Figure 13.2 Ć Info/Log UDC Information Display