Rockwell Automation 57C650 AutoMax Programming Executive Version 3.8 User Manual
Page 235
BĆ5
Processor Module Error and Status Codes
AutoMax DriveĆRelated Error Codes
The following error codes indicate a power circuit or external drive system fault.
They apply only to systems that incorporate DCS 5000 microĆregulators. After
correcting the problem, reset the Processor module by cycling power and
reĆloading the configuration task and application tasks to clear the error code.
Note that these error codes also appear in the Error Log for the Processor.
80
Instantaneous overcurrent fault
Ć armature current exceeded IOC_THRESH
value in CML task
81
Line sync loss fault
82
Tach loss fault
Ć 40% armature phase angle with less than 5% tach
feedback
83
Overspeed/overvoltage fault
Ć CML task OSV_FDBK exceeded OSV_THRESH
number
84
Hardware overspeed fault
Ć drive analog module potentiometer setting
exceeded by input voltage
85
External IET fault
Ć external fault input triggered
86
Phase rotation fault
Ć incorrect phasing
87
Shorted SCR detected in power module
Corrective action: troubleshoot power circuit and external drive system. These
errors do not cause a Stop All and do not require reĆloading the configuration or
application tasks.
Configuration Error Codes
The following error codes usually indicate a discrepancy between the actual
hardware configuration and the I/O definitions in the configuration for the rack.
E0
TASK specified in configuration uninstalled,
at wrong priority, of wrong type, on wrong
Processor module; wrong spelling of TASK
E1
Invalid configuration, configuration not successfully downloaded.
E2
I/O referenced in configuration is missing.
E3
I/O referenced in configuration is missing. Invalid configuration,
configuration not successfully downloaded.
E4
Error building task, insufficient memory in Processor Module.
Invalid configuration, configuration not successfully downloaded.
E5
Error building task, insufficient memory in Processor Module.
Invalid configuration, configuration not successfully downloaded.
E6
I/O referenced in configurations is missing. Error building task,
insufficient memory in Processor Module.
E7
Invalid configuration, configuration not successfully downloaded.
I/O referenced in configuration is missing. Invalid configuration,
configuration not successfully downloaded.
E8
Error installing application task, common symbol could not be
resolved, insufficient memory in Processor Module.
E9
Error installing application task, common symbol could not be
resolved, insufficient memory in Processor Module. Invalid
configuration, configuration not successfully downloaded.