Rockwell Automation Publication 825-UM004D-EN-P - November 2012

93

Configuring Protection & Logic Functions Chapter 6

Timer Function

When you assign an input contact and an output auxiliary relay to appropriate
parameters of Timer Function, the output responds to the change in input
contact with the characteristics shown in Figure 33.

This feature has the following application examples:

Time-graded switching on and off

Delaying the transfer of alarm and trip messages

Figure 33 - Operating Characteristics of Timer Functions

Front Panel Settings

Table 39 - Timer Settings

Setting Prompt

Setting Range

Factory Default

ON DELAY T1

0…240 s

0

OFF DELAY T1

0…240 s

0

ON DELAY T2

0…240 s

0

OFF DELAY T2

0…240 s

0

NOTE:

In addition to setting the On and Off Delays, you must assign TIMER1 and/or TIMER2 to a
control input (see Table 44). You must also assign TIMER1T and/or TIMER2T to auxiliary
output relays. See Table 43 for detail.

Table 40 - Front Panel Settings

Setting Prompt

Setting Range

Factory Default

LCD TIMEOUT

Off, 1…30 min

15

LCD CONTRAST

1…8

5

T on

T off

T off

T on

T off

Output
Relay Word
TIMER nT

Control Input

TIMER

Control Input

On-Delay

(T off = 0)

Off-Delay

(T on = 0)

On-Off-Delay

On-Off-Delay

T on

T on = On-delay
T off = Off-delay

n = 1 or 2

T on

T off