beautypg.com

Voltage-based protection, Undervoltage, Table 28 - undervoltage settings – Rockwell Automation 825-P Modular Protection System for Motors User Manual User Manual

Page 86

background image

86

Rockwell Automation Publication 825-UM004D-EN-P - November 2012

Chapter 6 Configuring Protection & Logic Functions

Provides an RTD Bias Alarm if the winding temperature exceeds 60°C rise
over ambient and the RTD % Thermal Capacity exceeds the thermal
element % Thermal Capacity by more than 10%.

As ambient temperature rises, the motor’s ability to shed heat to the surroundings
is reduced and internal temperatures rise. To preserve insulation life, NEMA
standards suggest a 1°C reduction in RTD Trip Temperature for each 1°C rise in
ambient temperature over 40°C.

When you enable RTD biasing, the 825-P automatically reduces the RTD Trip
Temperatures for all winding RTDs when ambient temperature is above 40°C.
The relay reduces the trip temperatures by 1°C for each degree rise in ambient
temperature over 40°C.

Finally, when you enable Thermal Model biasing, the relay provides an RTD

Bias Alarm when the RTD % Thermal Capacity exceeds the thermal element
% Thermal Capacity by more than 10 percentage points while the winding
temperature rise is higher than 60°C over ambient. This alarm can be a useful
indicator that the motor has lost coolant flow or that the winding RTD Trip
Temperature is conservatively low.

For all the RTD Thermal Capacity and bias calculations described above, the
relay uses the winding RTD whose measured temperature is closest to its trip
value.

Voltage-Based Protection

The following information applies to relay models with voltage inputs.

Undervoltage

EXAMPLE

Relay Calculation of RTD% Thermal Capacity

RTD%

Thermal

Capacity

Winding RTD

Temperature

Winding RTD Trip

Temperature

Ambient

Temperature

Ambient

Temperature

=

Table 28 - Undervoltage Settings

Setting Prompt

Setting Range

Factory Default

UV TRIP LEVEL

Off, 0.60…1.00 xVnm

Off

UV TRIP DELAY

0.0…120.0 s

0.0

UV WARN LEVEL

Off, 0.60…1.00 xVnm

Off

UV WARN DELAY

0.0…120.0 s

5.0