I/o configuration, Analog output, Table 35 - i/o settings – Rockwell Automation 825-P Modular Protection System for Motors User Manual User Manual

Page 90: Analog out sel, Load_i, Table 36 - scaling of analog output, Avg_i, Max_i, Therm, Wdg_rtd

background image

90

Rockwell Automation Publication 825-UM004D-EN-P - November 2012

Chapter 6 Configuring Protection & Logic Functions

The 825-P provides an ability to control external devices based on parameter
Load Control Selection. You can select Current, Power, or Thermal Capacity
Utilized to operate auxiliary outputs.

When the selected parameter exceeds the level set by Load Control Upper for one
second, the assigned auxiliary relay operates. The auxiliary relay resets when the
parameter drops below the upper level setting for one second.

When the selected parameter drops below the level set by Load Control Lower
for 1 second, the assigned auxiliary relay operates. The auxiliary relay resets when
the parameter is above the lower-level setting for 1 second.

You can use this feature to control the motor load within set limits.

I/O Configuration

Analog Output

The expansion I/O option provides a 4

20 mA DC analog current output with

a variety of output parameters. Use the Analog Output Select setting to select a
parameter from the list of available options. Table 36 shows description and
scaling of the output for different parameter selections.

NOTE:

Prompt of settings LD CTL UPPER and LD CTL LOWER are dependent on the LD CONTROL SEL
setting. All possible prompts are shown in Table 34.

NOTE:

In addition to setting the Load Control levels, you must assign LD CTL UPPER and LD CTL
LOWER to auxiliary output relays (one each); see Table 43, and Figure 16

for connection

diagrams.

Table 35 - I/O Settings

Setting Prompt

Setting Range

Factory Default

ANALOG OUT SEL

LOAD_I, AVG_I, MAX_I, %THERM, WDG_RTD, BRG_RTD, PWR_kW, PF

LOAD_I

Table 36 - Scaling of Analog Output

ANALOG OUT SEL

(AOPARM)

Description

Output Scaling (4 mA)(20 mA)

(Unit)

LOAD_I

Average Load Current

0.0…1.0 Per Unit of FLA

AVG_I

Average Load Current

0.2…2.0 Per Unit of FLA

MAX_I

Maximum of the Phase currents

0.2…2.0 Per Unit of FLA

%THERM

Percentage Thermal Capacity

0…100%TCU

WDG_RTD

Hottest Winding RTD Temperature

0…250°C

BRG_RTD

Hottest Bearing RTD Temperature

0…250°C

PWR_kW

Motor Power

0.0…1.0 per unit FLVA

PF

Motor Power Factor

0.8 Lag…0.8 Lead