beautypg.com

Voltage transformer (vt) configuration settings, Basic motor protection – Rockwell Automation 825-P Modular Protection System for Motors User Manual User Manual

Page 69

background image

Rockwell Automation Publication 825-UM004D-EN-P - November 2012

69

Configuring Protection & Logic Functions Chapter 6

Voltage Transformer (VT) Configuration Settings

Relays that are not equipped with phase voltage inputs will hide these settings
and disable voltage-based protection and metering functions.

Table 10 shows voltage settings for relay models with optional voltage inputs.

Table 10 - CT Configuration and Full Load Current Settings

These settings configure the optional relay voltage inputs to correctly measure
and scale the voltage signals. Calculate the Phase VT Ratio by dividing the
primary rating by the secondary rating.

When phase-to-phase PTs are connected to the relay, set XFMR Connection
equal to Delta. When phase-to-neutral PTs are connected to the relay, set XFMR
Connection equal to Wye.

Basic Motor Protection

Setting Prompt

Setting Range

Factory Default

PHASE VT RATIO

1…250

34.65

LINE VOLTAGE

100…30000V

4160

XFMR CONNECTION

Delta

Wye Delta

NOTE:

The line voltage setting is in primary volts.

EXAMPLE

Phase VT Ratio Setting Calculation:

Consider a Phase VT Ratio Setting calculation, consider a 4000V motor application
where 4200:120V rated voltage transformers (connected in open delta) are used.

Set the VT Ratio := 4200/120 := 35 and DELTA_Y := Delta

IMPORTANT

Settings associated with options or accessories (converter module, voltage input card,
expansion I/O card, RTD scanner) require their installation or connection prior to being
made available for configuration.

ATTENTION: Configuration of protection elements is not complete until the elements
are assigned to the trip or auxiliary relays. Refer to I/O Assignments for instructions.