Control circuits, 300v ac, 240v ac – Rockwell Automation 825-P Modular Protection System for Motors User Manual User Manual
Page 188: 120v ac, B300, Ac15, 5 ma @ 17v, 10000 no load operations, 10 ms, 8 ms (typical))
188
Rockwell Automation Publication 825-UM004D-EN-P - April 2012
Chapter A Specifications
Control Circuits
➊ Capacity at L/R = 40 ms
Supply
Rated Supply Voltage U
s
110…240V AC, 110…250V DC
24…48V DC
Operating Range
0.80…1.1 U
s
0.80…1.1 U
s
Rated Frequency (V AC)
50/60 Hz ± 5 Hz
Max. Power Consumption
AC: 15VA, DC: 15 W
Output Relays
Type of Contacts
Trip
Aux1…Aux 6
Form C DPDT
Form A SPDT – NO
Rated Insulation Voltage U
i
300V AC
Rated Operating Voltage U
e
240V AC
Rated Impulse Strength U
imp
4kV
Rated Thermal Current I
the
5 A
Rated Operating Current I
e
120V AC
240V AC
3 A
1.5 A
Contact Rating Designation
B300
Utilization Category
AC15
Contact Reliability
5 mA @ 17V
Mechanical Durability
10000 no load operations
Pickup Time
< 10 ms
Dropout Time
< 8 ms (typical))
DC Current Ratings ➊
24V DC
0.75 A
48V DC
0.50 A
125V DC
0.30 A
250V DC
0.20 A
Inputs
Rated Operating Voltage U
e
IN1 and IN2
IN3, IN4 and IN5
24V AC/DC
120V AC/DC (825-PIOD)
24V AC/DC (825-PIOR)
Operating Range
0.80…1.1 Ue
Rated Insulation Voltage U
i
300V AC
Rated Impulse Strength U
imp
4kV
Rated Frequency (AC)
50/60 Hz
±
5 Hz
On-State Voltage
15V
79V
On-State Current (turn-on)
2 mA
2 mA
Steady State Current
15 mA
15 mA
Off-State Voltage
5V
20V
Off-State Current
0.5 mA
1 mA