beautypg.com

Control circuits, 300v ac, 240v ac – Rockwell Automation 825-P Modular Protection System for Motors User Manual User Manual

Page 188: 120v ac, B300, Ac15, 5 ma @ 17v, 10000 no load operations, 10 ms, 8 ms (typical))

background image

188

Rockwell Automation Publication 825-UM004D-EN-P - April 2012

Chapter A Specifications

Control Circuits

➊ Capacity at L/R = 40 ms

Supply

Rated Supply Voltage U

s

110…240V AC, 110…250V DC

24…48V DC

Operating Range

0.80…1.1 U

s

0.80…1.1 U

s

Rated Frequency (V AC)

50/60 Hz ± 5 Hz

Max. Power Consumption

AC: 15VA, DC: 15 W

Output Relays

Type of Contacts

Trip
Aux1…Aux 6

Form C DPDT
Form A SPDT – NO

Rated Insulation Voltage U

i

300V AC

Rated Operating Voltage U

e

240V AC

Rated Impulse Strength U

imp

4kV

Rated Thermal Current I

the

5 A

Rated Operating Current I

e

120V AC
240V AC

3 A
1.5 A

Contact Rating Designation

B300

Utilization Category

AC15

Contact Reliability

5 mA @ 17V

Mechanical Durability

10000 no load operations

Pickup Time

< 10 ms

Dropout Time

< 8 ms (typical))

DC Current Ratings ➊

24V DC

0.75 A

48V DC

0.50 A

125V DC

0.30 A

250V DC

0.20 A

Inputs

Rated Operating Voltage U

e

IN1 and IN2

IN3, IN4 and IN5

24V AC/DC

120V AC/DC (825-PIOD)
24V AC/DC (825-PIOR)

Operating Range

0.80…1.1 Ue

Rated Insulation Voltage U

i

300V AC

Rated Impulse Strength U

imp

4kV

Rated Frequency (AC)

50/60 Hz

±

5 Hz

On-State Voltage

15V

79V

On-State Current (turn-on)

2 mA

2 mA

Steady State Current

15 mA

15 mA

Off-State Voltage

5V

20V

Off-State Current

0.5 mA

1 mA