Rockwell Automation 825-P Modular Protection System for Motors User Manual User Manual

Page 210

background image

210

Rockwell Automation Publication 825-UM004D-EN-P - April 2012

Chapter B Parameter List

I/O Settings

292

40193

400193

ANALOG OUT SEL

0 = Load_I

0

Get/Set

1 = %Therm

2 = Wdg_RTD

3 = Brg_RTD

4 = PF

5 = Pwr_kW

6 = Avg_I

7 = Max_I

293

40194

400194

TRIP INHIBIT

0 = Curr.Imbalance

0

Get/Set

1 = Jam

0

2 = Ground Fault

0

3 = Short Circuit

0

4 = Undercurrent

0

5 = Start Inhibit

0

6 = PTC

0

7 = RTD

0

294

40195

400195

RELAY BEHAVIOR

0 = Trip Fail-Safe

1

Get/Set

1 = Aux1 Fail-Safe

1

2 = Aux2 Fail-Safe

1

3 = Aux3 Fail-Safe

1

4 = Aux4 Fail-Safe

1

5 = Aux5 Fail-Safe

1

6 = Aux6 Fail-Safe

1

Timer

Settings

295

40196

400196

ON DELAY T1

0

240

0

1

s

Get/Set

296

40197

400197

OFF DELAY T1

0

240

0

1

s

Get/Set

297

40198

400198

ON DELAY T2

0

240

0

1

s

Get/Set

298

40199

400199

OFF DELAY T2

0

240

0

1

s

Get/Set

Front Panel

Set

299

40200

400200

LCD TIMEOUT

0 = Off

30

0

1

min

Get/Set

300

40201

400201

LCD CONTRAST

1

8

0

1

Get/Set

301

40202

400202

DISPLAY ENABLE

0 = Time & Date

0

Get/Set

1 = Ground Current

0

2 = Curr. Imbalance

0

3 = Frequency

0

4 = Therm Cap Used

0

5 = Volt Imbalance

0

6 = Power

0

7 = RTD Temp

0

Group

DeviceNet

Param No.

Modbus Register

Parameter Name

Min

Max

Default

Scale

Factor

Units

Access

Read (0x03h)

Write (0x06h)