beautypg.com

Mechanical ratings, Storage: -40…+85°c (-40…+185°f), Operating (open): -20…+60°c (-4…+140°f) – Rockwell Automation 825-P Modular Protection System for Motors User Manual User Manual

Page 189: 5…95% non-condensing, 2000 m, 30 g, 14…2.5 mm2/#20…12 awg, 79 n•m/7lb-in, Ip20, 4 n•m/12 lb-in

background image

Rockwell Automation Publication 825-UM004D-EN-P - April 2012

189

Specifications Chapter A

Mechanical Ratings

RTD Scanner Module

Environmental
Ambient Temperature

Storage: -40…+85°C (-40…+185°F)
Operating (open): -20…+60°C (-4…+140°F)

Humidity (Operating)

5…95% Non-condensing

Maximum Altitude

2000 m

Vibration (per IEC 68-2-6)

3 G

Shock (per IEC 68-2-27)

30 G

Control Terminals
Terminal Screw

M3

Cross Section (1 wire, stranded/solid)

0.14…2.5 mm

2

/#20…12 AWG

Torque

0.79 N•m/7lb-in

Degree of Protection

IP20

Ground Screw
Terminal Screw

#6

Torque

1.4 N•m/12 Lb-in

Supply
Rated Supply Voltage

U

s

110/240V AC

Operating Range

0.80…1.2

U

s

Rated Frequency

50/60 Hz ± 5 Hz

Max. Power Consumption

5 VA

Rated Insulation Voltage

U

i

300V AC

Rated Impulse Strength

U

imp

4kV

Pollution Degree

2

Environmental
Ambient Temperature Storage

Storage: -40…+85°C (-40…+185°F)
Operating: -20…+60°C (-4…+140°F)

Humidity (Operating)

5…95% Non-condensing

Maximum Altitude

2000 m

Vibration (per IEC 68-2-6)

3G

Shock (per IEC 68-2-27)

30G

Inputs
Number of input channels

12

Type

3-wire

Compatibility

CU10, NI100, NI120, PT100 (per IEC 60751: 1983)

Range

-50…250°C

Accuracy

± 2°C

Open Circuit Detection

> 250°C

Short Circuit Detection

< -50°C

Control Terminals
Terminal Screw

M3

Cross Section (1 wire, stranded/solid)

0.25…2.5mm

2

(24…12 AWG)

Torque

0.4…0.6 Nm (3.5…5.3 Lb-in)

Degree of Protection

1P20