Speed switch (stalling during start), Table 25 - speed switch settings, Figure 31 - stalling during starting – Rockwell Automation 825-P Modular Protection System for Motors User Manual User Manual

Page 82: Thermistor (ptc) monitoring, Table 26 - ptc settings, Speed switch (stalling, During start) thermistor (ptc) monitoring

background image

82

Rockwell Automation Publication 825-UM004D-EN-P - November 2012

Chapter 6 Configuring Protection & Logic Functions

Speed Switch (Stalling

During Start)

Speed Switch (stalling during start) protection provides mechanical sensing of a
locked rotor condition through input monitoring of a speed switch that is
mechanically coupled to the motor shaft. When the SS TRIP DELAY is set, the
relay trips if the speed switch is not closed within the set time after the motor
start begins. A separate delay, SS WARN DELAY, can also be set to provide a
warning before the Speed Switch trip. Figure 31 shows typical currents during
motor start (normal and stall during start) and the Speed Switch Trip Delay time
setting.

Figure 31 - Stalling During Starting

Thermistor (PTC) Monitoring

Table 25 - Speed Switch Settings

Setting Prompt

Setting Range

Factory Default

SS TRIP DELAY

Off, 1…240 s

Off

SS WARN DELAY

Off, 1…240 s

Off

NOTE:

In addition to setting the SS DELAY, you must connect the speed switch contact to an input
assigned to Speed Switch (see Table 44 and Figure 5, Figure 20, and Figure 21 for connection
diagrams).

I

1

2

I

tv

t

Ie

Ie

1 =

2 =

tv =

Normal Start without Hindrance
by High Overload or Stalling
Stalling During Standing
SS TRIP DELAY Time

Table 26 - PTC Settings

Setting Prompt

Setting Range

Factory Default

PTC ENABLE

Y, N

N

PTC RESET MODE

Man, Auto

Man