ASCII Serial Communications Chapter 12

TARGET R (Level 2)

The TARGET R command resets the front-panel tripping targets and releases
the trip signal if the fault condition has vanished and lockout conditions are not
present. If you issue the TARGET R command at the relay serial port or use the
front-panel Test/Reset push button and the relay tripping targets do not reset,
verify that the fault condition and all lockouts have cleared.

TIME (Level 1 or 2)

The TIME command displays the relay clock (24 hours). To set the clock, type
TIME hh:mm:ss

and then press Enter.

Separate the hours, minutes, and seconds with colons, semicolons, spaces,
commas, or slashes. For example, set 22:47:36 by typing

TIME 22:47:36

and

then pressing Enter:

View or Change Settings with
Front Panel Serial Port

View Settings

Use the SHOW command to view relay settings. The SHOW command is
available from Access Level 1 and Access Level 2.

Table 108 lists the SHOW command options.

You can append a setting name to each of the commands to specify the first
setting to display (e.g., SHO 50P1P displays the relay settings starting with
setting 50P1P). The default is the first setting.

The SHOW command displays only the enabled settings. To display all the
settings, including disabled/hidden settings, append an A to the SHOW
command (e.g., SHOW A).

Table 108 - SHOW Command Options

Command

Description

SHOW

Show relay settings.

SHO A

Show all relay settings: enabled, disabled/hidden.

SHO P

Show front serial port settings.

SHO M

Show I/O mapping settings.