beautypg.com

From the pull-down menu, select fault, Place the input to the left of the and function, Connect the input to the input 2 of the and latch – Rockwell Automation 825-P Modular Protection System for Motors User Manual User Manual

Page 127: From the toolbar, select network output point, From the pull-down menu, select flt reset, Select ok, Figure 45 - devicelogix logic editor screen, From the toolbar. select discrete output point

background image

Rockwell Automation Publication 825-UM004D-EN-P - November 2012

127

825-PDN DeviceNet Communication Card Chapter 9

18.

From the pull-down menu, select Fault.

19.

Place the input to the left of the AND function.

20.

Connect the input to the Input 2 of the AND latch.

21.

From the toolbar, select Network Output Point.

22.

From the pull-down menu, select Flt Reset.

23.

Select OK.

24.

Moving your cursor into the grid, place the Output to the right of the
AND

function block.

25.

Connect the Output of the AND function block to Flt Reset.

Figure 45 - DeviceLogix Logic Editor Screen

26.

From the toolbar. select Discrete Output Point.

27.

From the pull-down menu, select Aux Out 5. This is the tower light output
listed in the I/O table example.