D. enter access level 2, H. set the relay passwords with the pas command, Apply current and voltage signals to the relay – Rockwell Automation 825-P Modular Protection System for Motors User Manual User Manual

Page 185

background image

Rockwell Automation Publication 825-UM004D-EN-P - November 2012

185

Firmware Upgrade Instructions Chapter 13

d. Enter Access Level 2.
e. Issue

STATUS command, and verify that the relay status is OK.

f. Set the relay clock and calendar using the

DATE and TIME commands.

g. Set the Relay and Port settings using the following commands:

SET,

SET M, and SET P.

h. Set the relay passwords with the

PAS command.

10.

Set the communications software settings (baud rate, number of data bits,
number of stop bits) to agree with the port settings of the 825-P.

11.

Issue the

STATUS command, and then verify that all relay self-test results

are OK.

12.

Apply current and voltage signals to the relay.

13.

Issue the

METER command, and then verify that the current and voltage

signals are correct.

The relay is now ready for your commissioning procedure.