Rockwell Automation Publication 825-UM004D-EN-P - November 2012

Chapter 7 Metering & Monitoring

Instantaneous Metering

All angles are displayed between –180°…+180°. Delta-connected PT angles are
referenced to VAB or L1 and wye-connected PT angles are referenced to VAN or
L1. If the voltage channels are not supported or if VAB < 13V (for Delta) or
VAN < 13V (for Wye), PT angles are referenced to L1 current.

Thermal Metering

The thermal metering function reports the present values of the RTD input
temperatures and several quantities related to the motor overload protection
function (Table 47).

Table 46 - Measured Values

Relay Option

Meter Values

All Models

Line Currents L1, L2, and L3
IN (Core-Balance Ground Fault Current) magnitudes (A) and phase angles (°)

IG (Residual Ground Fault Current) magnitude (A) and phase angle (°)

IM (Average Current Magnitude)

Average Motor Load (x I

e

)

Current Imbalance %

System Frequency (Hz)

With Voltage Option

VAB, VBC, VCA or VAN, VBN, VCN, VG magnitudes (V) and phase angles (°)

Average Voltage (L-L or L-N)
Voltage Imbalance %

Real Power (kW)
Reactive Power (kVAR)

Apparent Power (kVA)
Power Factor
Real Energy (MWh)
Reactive Energy (MvARh)
Apparent Energy (MvAh)

Table 47 - Thermal Meter Values

Relay Option

Thermal Values

All Models

Average Motor Load (x I

e

)

Thermal Capacity Used %

Time to Trip (s)

Time to Reset (min)

Starts Available

With External 825-PR12D Module

All RTD Temperatures

RTD % Thermal Capacity

NOTE:

If the Overload Protection is disabled, the relay always reports % Thermal Capacity = 999
and Calculated Time to Thermal Trip (s) = 9999.