Get/set, 0x05, 0x0e – Rockwell Automation 825-P Modular Protection System for Motors User Manual User Manual
Page 254: 0x10, Reset, Get_attribute_single, Set_attribute_single, Discreet input point object - class code 0x0008, Revision, Max instance
254
Rockwell Automation Publication 825-UM004D-EN-P - April 2012
Chapter E DeviceNet Information
Instances 5…7 are available group 3 explicit message connections that are
allocated through the UCMM. The following attributes are supported:
The following services are implemented for the Connection Object:
Discreet Input Point Object -
CLASS CODE 0x0008
The following class attributes are supported for the Discrete Input Point Object:
Attribute ID
Access Rule
Name
Data Type
Value
1
Get
State
USINT
0 = nonexistant
1 = configuring
3 = established
4 = timed out
2
Get
Instance Type
USINT
0 = Explicit Message
3
Get
Transport Class Trigger
USINT
0x83 - Server, Transport Class 3
4
Get
Produced Connection ID
UINT
Depends on message group
and Message ID
5
Get
Consumed Connection ID
UINT
Depends on message group
and Message ID
6
Get
Initial Comm Characteristics
USINT
0x33 (Group 3)
7
Get
Produced Connection Size
UINT
0
8
Get
Consumed Connection Size
UINT
9
Get/Set
Expected Packet Rate
UINT
in milliseconds
12
Get
Watchdog Action
USINT
01 = auto delete
03 = deferred delete
13
Get
Produced Connection Path Length
UINT
0
14
Get
Produced Connection Path
Empty
15
Get
Consumed Connection Path Length
UINT
0
16
Get
Consumed Connection Path
Empty
Service Code
Implemented for:
Service Name
Class
Instance
0x05
No
Yes
Reset
0x0E
No
Yes
Get_Attribute_Single
0x10
No
Yes
Set_Attribute_Single
Attribute ID
Access Rule
Name
Data Type
Value
1
Get
Revision
UINT
2
2
Get
Max Instance
UINT
2, 5, or 8