Chapter 8 Analyzing Events

Table 50 - Example SER Report Explanations

Item #

Explanation

11, 10, 9, 8, 7

After a 10-second accelerating time, the motor relay indicates the motor is running (9).
Later, the ambient temperature alarm element asserts.

6, 5

The ambient temperature trip element times out, causing the relay to trip. Trip

is asserted.

4, 3

Declining temperature allows the elements to drop out.

2, 1

As the current continues to drop, the relay declares the motor stopped.