beautypg.com

Example reports, Event summary report, Figure 36 - example event summary report – Rockwell Automation 825-P Modular Protection System for Motors User Manual User Manual

Page 111: Serialized events recording (ser) report, Figure 37 - example ser report

background image

Rockwell Automation Publication 825-UM004D-EN-P - November 2012

111

Analyzing Events Chapter 8

Example Reports

Event Summary Report

The example event summary report in Figure 36 corresponds to the example
Serialized Events Recording (SER) report in Figure 37.

Figure 36 - Example Event Summary Report

=>SUM

825-P Modular Date: 06/07/2003 Time:

14:50:06:032

Prot. System

Event #: 1 Event: No Trip

Event Date: 06/07/2003 Event Time: 14:39:47:907

L1 L2 L3 RES CB

CURRENT MAG (A): 259.7 191.6 190.6 0.1 68.2

VAN VBN VCN VG

VOLTAGE MAG L-N (V): 458 460 457 456

Serialized Events Recording (SER) Report

The example SER report in Figure 37 includes records of events that occurred
before the beginning of the event summary report in Figure 36. The SER event
report rows are explained in Table 50, numbered in correspondence to the Item #
column.

Figure 37 - Example SER Report

=>

SER

825-P Modular Date: 07/07/2003 Time: 14:50:04.744

Prot. System

FID=825-Modular xxxx-Vxxxx-Zxxxxxx-Dxxxxxxxxx

# DATE

TIME

ELEMENT

STATE

11

06/07/2003

14:34:32.786

STOPPED

Deasserted

10

06/07/2003

14:34:32.786

STARTING

Asserted

9

06/07/2003

14:34:42.795

RUNNING

Asserted

8

06/07/2003

14:34:42.795

STARTING

Deasserted

7

06/07/2003

14:39:45.398

AMBALRM

Asserted

6

06/07/2003

14:39:47.907

AMBTRIP

Asserted

5

06/07/2003

14:39:47.907

TRIP

Asserted

4

06/07/2003

14:39:48.007

AMBTRIP

Deasserted

3

06/07/2003

14:39:48.007

AMBALRM

Deasserted

2

06/07/2003

14:39:48.028

STOPPED

Asserted

1

06/07/2003

14:39:48.028

RUNNING

Deasserted