Example reports, Event summary report, Figure 36 - example event summary report – Rockwell Automation 825-P Modular Protection System for Motors User Manual User Manual
Page 111: Serialized events recording (ser) report, Figure 37 - example ser report

Rockwell Automation Publication 825-UM004D-EN-P - November 2012
111
Analyzing Events Chapter 8
Example Reports
Event Summary Report
The example event summary report in Figure 36 corresponds to the example
Serialized Events Recording (SER) report in Figure 37.
Figure 36 - Example Event Summary Report
=>SUM
825-P Modular Date: 06/07/2003 Time:
14:50:06:032
Prot. System
Event #: 1 Event: No Trip
Event Date: 06/07/2003 Event Time: 14:39:47:907
L1 L2 L3 RES CB
CURRENT MAG (A): 259.7 191.6 190.6 0.1 68.2
VAN VBN VCN VG
VOLTAGE MAG L-N (V): 458 460 457 456
Serialized Events Recording (SER) Report
The example SER report in Figure 37 includes records of events that occurred
before the beginning of the event summary report in Figure 36. The SER event
report rows are explained in Table 50, numbered in correspondence to the Item #
column.
Figure 37 - Example SER Report
=>
SER
825-P Modular Date: 07/07/2003 Time: 14:50:04.744
Prot. System
FID=825-Modular xxxx-Vxxxx-Zxxxxxx-Dxxxxxxxxx
# DATE
TIME
ELEMENT
STATE
11
06/07/2003
14:34:32.786
STOPPED
Deasserted
10
06/07/2003
14:34:32.786
STARTING
Asserted
9
06/07/2003
14:34:42.795
RUNNING
Asserted
8
06/07/2003
14:34:42.795
STARTING
Deasserted
7
06/07/2003
14:39:45.398
AMBALRM
Asserted
6
06/07/2003
14:39:47.907
AMBTRIP
Asserted
5
06/07/2003
14:39:47.907
TRIP
Asserted
4
06/07/2003
14:39:48.007
AMBTRIP
Deasserted
3
06/07/2003
14:39:48.007
AMBALRM
Deasserted
2
06/07/2003
14:39:48.028
STOPPED
Asserted
1
06/07/2003
14:39:48.028
RUNNING
Deasserted