Configure your terminal emulation software, Serial port settings – Rockwell Automation 825-P Modular Protection System for Motors User Manual User Manual
Page 163
Rockwell Automation Publication 825-UM004D-EN-P - November 2012
163
ASCII Serial Communications Chapter 12
Configure Your Terminal Emulation Software
Personal computers use terminal emulation software to send and interpret
received characters at the EIA-232 serial port. This software allows you to type
letters and numbers to form commands at the computer keyboard and to see the
characters you type and the relay responses on the computer screen. To ensure
the PC communicates correctly with the relay, configure the terminal emulation
software connection properties to match the relay serial port configuration.
Configure the terminal emulation software to match the default settings shown
in Table 96. For the best display, use VT-100 terminal emulation. If VT-100 is
not available, WYSE-100 and ANSI terminal emulations also work.
To change the port settings, use the front-panel
SET/SHOW > PORT settings
menu item.
Serial Port Settings
The 825-P provides settings that allow you to configure the communication
parameters for the front-panel serial port. The front-panel serial port supports
only ASCII communications.
Table 95 - Pin Functions and Definitions for EIA-232 Serial Port (Port F)
Pin
Pin Function
Definition
1, 4, 6
N/C
No connection
2
RXD, RX
Receive data
3
TXD, TX
Transmit data
5, 9
GND
Signal ground
7
RTS
Request to send
8
CTS
Clear to send
Table 96 - 825-P Relay Serial Communications Default Settings
Setting
Default
Speed (bps)
9600
Data Bits
8
Parity
N
Stop Bits
1
Flow Control
XON/XOFF (software flow control)