beautypg.com

Table 12 - motor codes, 4 and up – Rockwell Automation 825-P Modular Protection System for Motors User Manual User Manual

Page 72

background image

72

Rockwell Automation Publication 825-UM004D-EN-P - November 2012

Chapter 6 Configuring Protection & Logic Functions

If the Locked Rotor Ampere rating for the motor is unknown, but the motor

has a Motor Code designation, use the following table as provided by NEMA
(National Electrical Manufacturer Association) to determine the locked rotor
ampere value.

Locked kVA per horsepower range includes the lower figure up to, but not including, the higher figure; e.g., 3.14 is designated by letter

A and 3.15 is designated by letter B.

EXAMPLE

Thermal Element Setting

A 4000V 600 Hp motor is protected using the 825-P Thermal Overload Element. Motor
data sheet includes the following:

Rated Horsepower = 600 Hp

Rated Voltage = 4000V

Rated Full Load Current = 80 A

Rated Locked Rotor Amps = 480 A

Safe Stall Time at 100% Volts:

Cold = 18 seconds

Hot = 15 seconds

Service Factor = 1.2

Phase current transformers with 100:5 A rating and the MCM20 module are selected
for application. 825-P settings for application are calculated as shown below:

Current Transformer Ratio: := 100/5 := 20

Full Load Amps (Ie): := 80 A primary

Service Factor: := 1.2

Locked Rotor Amps: := 480.0/80.0 := 6.0 x Ie

Hot Locked Rotor Time: := 15.0 seconds

Run state time constant: := Auto

NOTE:

To prevent nuisance tripping from occurring when a motor operates at the rated service
factor, set Service Factor to 0.01 plus the motor nameplate value.

Table 12 - Motor Codes

Letter Designation

kVA/HP

Letter Designation

kVA/HP

A

0…3.15

L

9.0…10.0

B

3.15…3.55

M

10.0…11.2

C

3.55…4.0

N

11.2…12.5

D

4.0…4.5

P

12.5…14.0

E

4.5…5.0

R

14.0…16.0

F

5.0…5.6

S

16.0…18.0

G

5.6…6.3

T

18.0…20.0

H

6.3…7.1

U

20.0…22.4

J

7.1…8.0

V

22.4 and up

K

8.0…9.0