Rockwell Automation Publication 825-UM004D-EN-P - April 2012
Chapter A Specifications
Electromagnetic
Compatibility
➊
Performance Criteria 1 requires the DUT to experience no degradation or loss of performance.
➋
Environment 2.
Metering Accuracy
Standards
CSA 22.2 No. 14, EN60947-5-1, UL 508
Processing
Test Level
Performance Criteria
Electrostatic Discharge Immunity
8kV Air Discharge
6kV Contact Discharge
➊➋
RF Immunity
10V/m
➊➋
Electrical Fast Transient/Burst Immunity
4kV (Power)
2kV (Control and Comms)
➊➋
Surge Immunity
2kV L-E
1kV L-L
➊➋
Emissions
Radiated
Class A
Class A
Conducted
Phase Currents
+2%
Average Current
+2%
Average Motor Load
+2%
Current Imbalance
+2%
Ground Fault Current (Residual)
+2%
Ground Fault Current (Core Balance)
+2%
Frequency
+0.1 Hz
Line-to-Line Voltages
+2%
Average Line-to-Line Voltage
+2%
Line-to-Neutral Voltages
+2%
Average Line-to-Neutral Voltages
+2%
Voltage Imbalance
+2%
Real 3-Phase Power (kW)
+5%
Reactive 3-Phase Power (kVAR)
+5%
Apparent 3-Phase Power (kVA)
+2%
Power Factor
+2%
RTD Temperatures
+2° C
AC Current and Voltage Inputs:
16 samples per power system cycle
Digital Filtering:
One cycle full cosine after low-pass analog filtering. Net filtering
(analog plus digital) rejects DC and all harmonics greater than the
fundamental.
Protection and Control:
4 times per power system cycle